Описание
Оригинално описание
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
Засегнати продукти
- Honeywell IQ4E: v3.50_3.44 до 4.36 (build 4.3.7.9)
- Honeywell IQ412: v3.50_3.44 до 4.36 (build 4.3.7.9)
- Honeywell IQ422: v3.50_3.44 до 4.36 (build 4.3.7.9)
- Honeywell IQ4NC: v3.50_3.44 до 4.36 (build 4.3.7.9)
- Honeywell IQ41x: v3.50_3.44 до 4.36 (build 4.3.7.9)
- Honeywell IQ3: v3.50_3.44 до 4.36 (build 4.3.7.9)
- Honeywell IQECO: v3.50_3.44 до 4.36 (build 4.3.7.9)
Вид слабост
История
- 12 март 2026 Публикувано